Suitable for UPS applications, power systems, radio and television systems, switchgear, industrial program control, renewable energy (solar / wind energy), emergency lighting, etc.
Product design life 2V ≥ 12 years, 12V ≥ 10 years (25 ℃)
Product advantages
·AGM backup battery has higher integrity, safety and reliability
·Excellent high rate discharge performance
·Under the conditions of floating charge and controlled ambient temperature, the design life can reach 2V ≥ 12 years and 12V ≥ 10 years
·The very high energy density allows a more compact battery layout
·Fully comply with product and Safety specifications
·Internal gas recombination efficiency reaches 99%
·No separate battery room is required
·Maintenance free without water
·No harm to air / sea / rail / road transportation
·Recyclable
Technical features
·Paste coated thick electrode plate of lead tin calcium alloy grid makes the corrosion of electrode plate less and prolongs the service life
·The electrolyte is adsorbed in the microporous glass fiber "AGM" partition
·Internally threaded copper core terminals ensure conductivity, greater torque retention and easy installation
·The through wall welding connection between monomers makes the internal resistance of the connected battery smaller
·Pole seal design, separate O-ring and epoxy resin seal to prevent acid leakage in a wide temperature range
·Each unit is equipped with a one-way safety valve to allow the discharge of excess gas caused by overcharge and prevent sparks or open flames from entering the battery
·High strength ABS groove cover material ensures the mechanical strength that can not be exceeded, and flame retardant ABS plastic can be selected
·The monthly self discharge (25 ℃) is less than 2%, allowing 6 months of storage time
Electrical performance characteristics
·Floating charge voltage (25 ℃) 2.23 ~ 2.27v/cell for standby
·Equalizing voltage: 2.35 ~ 2.4v/cell
·Charging current: 0.25c10a
·Floating charge voltage temperature compensation coefficient: - 0.3mv/cell
·Self discharge (25 ℃): < 2% / month
Apply
·UPS system
·Power system
·Industrial and process control
·Emergency power supply system
·Electrical facilities
·Switchgear
·Renewable energy (solar / wind)